IEC 60227 01(BV) 450/750V Single-core Non-sheathed Rigid Conductor Cable

450/750V Single-core Non-sheathed Rigid Conductor Cable

APPLICATION
IEC 60227 01 (BV) Single-core Non-sheath with rigid conductor cable used for general purposes.
IEC 60227 01 of hook up wire is also used in power installation,household electrical appliance,instrument, Telecommunications equipment,switch control, relay and instrumentation panels of power switchgear and for purposes such as internal connectors in rectifier equipment,motor starters and controllers.

CABLE STANDARDS
IEC 60227,BS,DIN,ICEA up on request.

18

 

 

BASIC INFORMATION
Code Name
60227 IEC 01
Rated Voltage (Uo/U)
450/750V
Cable Structure
CU/PVC Insulation

CONSTRUCTION
Conductor
Number of conductors:1
The conductors shall comply with the requirement given in IEC 60228 for class 1 or 2.
– class 1 for solid conductors;
– class 2 for stranded conductors.
Insulation
PVC(Polyvinyl Chloride) Type PVC/C according to IEC

CHARACTERISTICS
Conductor temperature
Maximum conductor temperature in normal use: 70℃
Installation temperature
Ambient temperature under installation shall not be below 0℃
Minimum bending radius
The bending radius of cable: (D-Diameter of cable)
D≤25mm——————≥4D
D>25mm——————≥6D

Nominal Cross Sectional Area(mm²)CENELEC CodeNO. of CoresClass of ConductorMax.Overall Diameter (mm)
1.5H07V-U113.2
2.5H07V-U113.9
4H07V-U114.4
6H07V-U115
10H07V-U116.4
1.5H07V-R123.3
2.5H07V-R124
4H07V-R124.6
6H07V-R125.2
10H07V-R126.7
16H07V-R127.8
25H07V-R129.7
35H07V-R1210.9
50H07V-R1212.8
70H07V-R1214.6
95H07V-R1217.1
120H07V-R1218.8
150H07V-R1220.9
185H07V-R1223.3
240H07V-R1226.6
300H07V-R1229.6
400H07V-R1233.2